Podcast
Questions and Answers
Under what circumstances is the use of nonmetallic boxes permitted with metal raceways or metal-armored cables?
Under what circumstances is the use of nonmetallic boxes permitted with metal raceways or metal-armored cables?
- When the nonmetallic box is used in a dry location.
- If the metal raceways or cables are used for low-voltage applications.
- If the metal raceways or cables are coated with a non-conductive material.
- Only when internal bonding means are provided between all entries in the box. (correct)
What is the primary requirement for screws or fasteners installed in the field that enter wiring spaces within boxes?
What is the primary requirement for screws or fasteners installed in the field that enter wiring spaces within boxes?
- They should be at least 1 inch long to ensure secure fastening.
- They must be made of stainless steel to prevent corrosion.
- They must be painted a bright color for easy identification.
- They must be provided or specified by the manufacturer or comply with specific requirements. (correct)
What characteristic must boxes, conduit bodies, outlet box hoods, and fittings have to be installed in wet locations?
What characteristic must boxes, conduit bodies, outlet box hoods, and fittings have to be installed in wet locations?
- Be constructed of non-corrosive material.
- Have a minimum IP65 rating.
- Be listed for use in wet locations. (correct)
- Have a smooth, reflective surface to repel water.
What are the requirements for approved drainage openings installed in boxes or conduit bodies listed for use in damp or wet locations?
What are the requirements for approved drainage openings installed in boxes or conduit bodies listed for use in damp or wet locations?
When calculating the volume of a wiring enclosure (box), how should securely installed barriers within the box be treated?
When calculating the volume of a wiring enclosure (box), how should securely installed barriers within the box be treated?
What volume allowance is required for small fittings such as locknuts and bushings when calculating conductor fill in a box?
What volume allowance is required for small fittings such as locknuts and bushings when calculating conductor fill in a box?
According to conductor fill requirements within boxes, what allowance is made for an equipment grounding conductor?
According to conductor fill requirements within boxes, what allowance is made for an equipment grounding conductor?
What condition must be met for conduit bodies to contain splices, taps, or devices?
What condition must be met for conduit bodies to contain splices, taps, or devices?
In installations using metal boxes or conduit bodies with conductors unprotected by flexible tubing, what is required for individual openings?
In installations using metal boxes or conduit bodies with conductors unprotected by flexible tubing, what is required for individual openings?
When flexible tubing is used to enclose conductors entering a box or conduit body, how far must the tubing extend inside the enclosure?
When flexible tubing is used to enclose conductors entering a box or conduit body, how far must the tubing extend inside the enclosure?
Flashcards
Round Box Restriction
Round Box Restriction
Round boxes are prohibited when connecting conduits or connectors that require locknuts or bushings to the side of the box.
Wet Location Box Requirements
Wet Location Box Requirements
In damp or wet locations, boxes and fittings must prevent moisture from entering or accumulating.
Box Fill Requirement
Box Fill Requirement
Boxes must be sized to provide enough free space for all enclosed conductors, following fill calculations.
Conductor Count Rule
Conductor Count Rule
Signup and view all the flashcards
Yoke/Strap Volume Allowance
Yoke/Strap Volume Allowance
Signup and view all the flashcards
Marked Conduit Body
Marked Conduit Body
Signup and view all the flashcards
Insulated Entry Points
Insulated Entry Points
Signup and view all the flashcards
Candidate Bulletin
Candidate Bulletin
Signup and view all the flashcards
Test Information Portal
Test Information Portal
Signup and view all the flashcards
Study Notes
- Round boxes are disallowed where locknuts/bushings connect conduits/connectors to the box side.
- Exception 1: Nonmetallic boxes are allowed with metal raceways/cables if internal bonding is provided between all entries.
- Exception 2: Listed nonmetallic boxes with integral bonding and provision for attaching an equipment bonding jumper are permitted with metal raceways/cables.
- Nonmetallic boxes are suitable for open wiring on insulators, concealed knob-and-tube wiring, nonmetallic-sheathed cables, flexible cords, and nonmetallic raceways.
- Metal boxes need grounding/bonding as per Article 250, Parts I, IV, V, VI, VII, and X, unless 250.112(I) permits otherwise.
- Exception: Longer screws are acceptable if the end is protected by an approved method.
- Field-installed screws/fasteners in wiring spaces must be manufacturer-provided/specified or meet requirements.
- In damp/wet locations, boxes, conduit bodies, outlet box hoods, and fittings must prevent moisture entry/accumulation.
- Boxes, conduit bodies, outlet box hoods, and fittings in wet locations must be listed for wet locations.
- Approved drainage openings (3 mm to 6 mm diameter) can be field-installed in boxes/conduit bodies listed for damp/wet locations.
- Listed drain fittings can have larger openings if installed per manufacturer's instructions.
Number of Conductors
- Refer to 430.12 for motor/generator terminal housing volume requirements.
- Boxes/conduit bodies enclosing 4 AWG or larger conductors must also comply with 314.28.
- Outlet and device boxes must also comply with 314.24.
- Boxes/conduit bodies must be sized to ensure adequate free space for all enclosed conductors.
- Box volume, calculated per 314.16(A), must be at least equal to the fill calculation in 314.16(B).
- Minimum volume for conduit bodies is calculated in 314.16(C).
- Where no volume allowances are required by 314.16(B)(2) through (B)(6).
Box Volume
- Wiring enclosure volume is the total volume of assembled sections (plaster rings, domed covers, extension rings, etc.), marked with their volume or from Table 314.16(A).
- If a box has securely installed barriers, the volume is apportioned to each space. Metal barriers take up 8.2 cm3, nonmetallic barriers take up 16.4 cm3.
- Boxes 1650 cm3 or less (excluding Table 314.16(A) boxes) and nonmetallic boxes must be durably and legibly marked with their volume(s) by the manufacturer.
- Boxes in Table 314.16(A) with volumes exceeding the designated volume, they can have their volume marked as required.
- Volumes in 314.16(B)(1) through (B)(6) are added together.
- No allowance is needed for small fittings like locknuts and bushings.
- Each space within a box with a barrier is calculated separately.
- Exception: Equipment grounding conductors (up to four), fixture wires smaller than 14 AWG, or both, can be omitted from calculations if entering a box from a domed luminaire/canopy and terminating within.
Conductor Fill
- Each conductor originating outside the box and terminating/splicing within is counted once.
- Each conductor passing through the box without splice/termination is counted once.
- Each loop/coil of unbroken conductor (at least twice the minimum length per 300.14) is counted twice.
- Conductor fill is calculated using Table 314.16(B)(1).
- Conductors entirely within the box are not counted.
- With one or more internal cable clamps, use a single volume allowance from Table 314.16(B)(1) based on the largest conductor.
- No allowance is needed for cable connectors with clamping mechanisms outside the box.
- For luminaire studs/hickeys, use a single volume allowance per type of fitting based on the largest conductor.
- For each yoke/strap with devices/equipment, use a double volume allowance based on the largest conductor connected to the device(s)/equipment.
- Devices/equipment wider than a single 50 mm device box (Table 314.16(A)) require double volume allowances for each gang needed for mounting.
- Up to four equipment grounding conductors require a single volume allowance based on the largest equipment grounding conductor.
- Each additional equipment grounding conductor requires a volume allowance based on the largest equipment grounding conductor..
- A single volume allowance is required for each terminal block assembly based on the largest conductor(s) terminated to the assembly.
Splices, Taps and Devices
- Conduit bodies with splices, taps, or devices must be durably and legibly marked with their volume by the manufacturer.
- The maximum number of conductors is calculated per 314.16(B).
- Conduit bodies must be rigidly and securely supported.
- For messenger-supported wiring, open wiring on insulators, or concealed knob-and-tube wiring, conductors must enter the box through individual holes.
Metal Boxes
- In metal boxes/conduit bodies with conductors unprotected by flexible tubing, openings must have insulating bushings.
- With flexible tubing, extend the tubing from the last insulating support to at least 6 mm inside the box/conduit body and 6 mm beyond any cable clamp.
- The wiring method must be secured to the box or conduit body.
- Boxes/conduit bodies used as pull or junction boxes must comply with 314.28(A) through (E).
Exception
- Terminal housings provided with motors are exempt.
- Boxes/conduit bodies used as pull or junction boxes must comply with 314.28(A) through (E).
- Exception: Terminal housings supplied with motors.
Studying That Suits You
Use AI to generate personalized quizzes and flashcards to suit your learning preferences.