Codeology Lesson 7: NEC Chapter 7 Flashcards
21 Questions
135 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is acceptable for the wiring of an optional standby system installed in the same raceway as the general wiring system?

Acceptable 702.10

A Class 1 power-limited circuit shall be supplied by a source that has a rated output of not more than 30 volts and _____?

1,000 VA 725.41(A)

Upon failure of the normal supply, a legally required standby system is required to be available in _____ or less.

60 seconds 701.12

Optional standby systems are intended to supply on-site generated power to selected loads either automatically or manually.

<p>True</p> Signup and view all the answers

Copper or aluminum solid or stranded conductors are permitted to be used for the installation of non-power-limited fire alarm circuits.

<p>False</p> Signup and view all the answers

Select the voltage(s) below that may supply a Class 1 non-power-limited circuit. I. 24 V II. 120 V III. 277 V IV. 600 V V. 1,000 V

<p>I. 24 V, II. 120 V, III. 277 V, IV. 600 V</p> Signup and view all the answers

Where an emergency system is installed in accordance with the NEC, the source of power must be available within _____ of the loss of the normal supply.

<p>10 seconds 700.12</p> Signup and view all the answers

An installation calls for plenum-rated optical fiber cable to be installed. Which of the following cable types may be used for the installation?

<p>None of the above</p> Signup and view all the answers

Branch-circuit overcurrent protective devices in a legally required standby circuit shall be _____?

<p>accessible to authorized persons 701.30</p> Signup and view all the answers

Class 2 cables shall have a minimum voltage rating of _____?

<p>150 V 725.179(G)</p> Signup and view all the answers

The disconnecting means of the output of each DC source of a microgrid shall be _____?

<p>Both B and C</p> Signup and view all the answers

Fire-resistive cable assemblies shall be marked on their surface with the system type and the suffix _____?

<p>FRR 728.120</p> Signup and view all the answers

EMT is used to support power-limited fire alarm conductors.

<p>False</p> Signup and view all the answers

A(n) _____ must identify 15-ampere non-locking receptacles supplied by a COPS where other systems are present.

<p>illuminated face 708.10(A)(2)</p> Signup and view all the answers

Energy storage systems can include _____?

<p>All of the above</p> Signup and view all the answers

Instrumentation tray cable with 22 AWG conductors has a maximum ampacity of _____?

<p>3 A 727.8</p> Signup and view all the answers

Load shedding provided by an energy management system shall not override the power supplied to which of the following?

<p>All of the above</p> Signup and view all the answers

When connecting multiple sources of power in parallel with a primary source such as a utility, which article(s) must be consulted?

<p>Article 705 705.1</p> Signup and view all the answers

A solar installation will be built to power a cabin that is off-grid. Which article(s) need to be consulted?

<p>Article 690 and Article 705</p> Signup and view all the answers

Where Class 2 circuit conductors are in the same enclosure serving the same system as 120-volt power conductors, the conductors of the two systems shall be separated by _____?

<p>0.25&quot; 725.136(D)</p> Signup and view all the answers

Emergency circuit raceway systems that are exposed shall be identified and marked every _____?

<p>25' 700.10(A)(2)</p> Signup and view all the answers

Study Notes

NEC Chapter 7: Special Conditions

  • Optional standby systems can share raceways with general wiring systems, as per NEC 702.10.
  • Class 1 power-limited circuits should be powered by sources rated at a maximum of 30 volts and 1,000 VA (NEC 725.41(A)).
  • Legally required standby systems must be operational within 60 seconds of normal supply failure (NEC 701.12).
  • Optional standby systems are designed to provide generated power to specific loads, either automatically or manually (NEC 702.2).
  • Non-power-limited fire alarm circuits can only use copper or aluminum conductors if stated otherwise (NEC 760.49(C): False).
  • Class 1 non-power-limited circuits can be powered by 24 V, 120 V, 277 V, and 600 V (NEC 725.41(B)).
  • Emergency systems must have power available within 10 seconds of losing normal supply (NEC 700.12).
  • Plenum-rated optical fiber cable installation is restricted to specific types; if not listed, none are permitted (NEC 770.154).
  • Branch-circuit overcurrent protective devices in legally required standby circuits must be accessible to authorized persons (NEC 701.30).
  • Class 2 cables require a minimum voltage rating of 150 V (NEC 725.179(G)).
  • Disconnects for each DC source in a microgrid must meet specific requirements (NEC 712.34).
  • Fire-resistive cable assemblies must be marked with the system type and the suffix "FRR" (NEC 728.120).
  • EMT cannot be used to support power-limited fire alarm conductors (NEC 760.143: Violation).
  • An illuminated face must identify 15-ampere non-locking receptacles supplied by a Circuit Overcurrent Protective System (COPS) (NEC 708.10(A)(2)).
  • Energy storage systems encompass a range of components (NEC 706.2: all of the above).
  • Instrumentation tray cable with 22 AWG conductors has a maximum ampacity of 3 A (NEC 727.8).
  • Energy management systems must ensure power supply to essential functions during load shedding (NEC 750.30(A): All of the above).
  • Article 705 must be consulted for connecting parallel power sources to utility power (NEC 705.1).
  • Solar installations for off-grid cabins must refer to Article 690 for regulations (NEC 690.1: both a. and d.).
  • Class 2 circuit conductors and 120-volt power conductors must maintain a separation of 0.25 inches when in the same enclosure (NEC 725.136(D)).
  • Exposed emergency circuit raceway systems must be marked and identified every 25 feet (NEC 700.10(A)(2)).

Studying That Suits You

Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

Quiz Team

Description

Test your knowledge with flashcards based on NEC Chapter 7, which deals with special conditions in electrical wiring. Each card presents key concepts and definitions necessary for understanding optional standby systems and Class 1 power-limited circuits. Perfect for students or professionals looking to reinforce their knowledge of electrical codes.

More Like This