What forms of I/O does the C300 controller support through its two I/O links?

  • Only Analog Input and Output modules
  • Series C I/O and Process Manager I/O (correct)
  • Only Low Level Analog Input modules
  • Digital Output and Pulse Input modules only
  • Which module is specifically designed to interface with pulsed output transducers?

  • Pulse Input module (correct)
  • Analog Output module
  • Digital Output module
  • Universal Input Output module
  • What is the function of the Series C Profibus Gateway module?

  • To establish communication with profibus devices (correct)
  • To connect Fieldbus devices to the C300 controller
  • To provide redundancy for the I/O modules
  • To interface with Allen Bradley PLCs
  • Which interface allows the C300 controller to access Allen Bradley PLCs?

    <p>Fault Tolerant Ethernet Bridge</p> Signup and view all the answers

    How can redundancy be applied to the I/O modules of the C300 controller?

    <p>Redundancy is an option for all modules except Low Level MUX</p> Signup and view all the answers

    Study Notes

    C300 Series C Input Output Options

    • The C300 controller supports two I/O links, each link consisting of I/O hardware connected to the controller by two I/O link interface cables.
    • Each I/O link can be configured to support either Series C I/O or Process Manager I/O
    • Series C I/O includes Analog Input, Analog Output, Digital Input, Digital Output, Pulse Input, Universal Input Output, Low Level MUX I/O and Low Level Analog Input modules.
    • Analog In and Analog Out modules support Hart.
    • All modules except the Low Level MUX can be optionally redundant.
    • The pulse Input module is used to interface with pulsed output transducer like tachometers, flow meters.
    • Fieldbus devices are interfaced to the C300 controller through the Series C Fieldbus Interface, which is also designed in the Series C form factor.
    • The C300 controller also supports the same I/O modules from the Process manager family like AI, AO, DI, DO, RTD, T/C, DI SOE.
    • A Fault Tolerant Ethernet Bridge connection brings all Series A I/O modules into the C300 controller.
    • Series C Profibus Gateway module is used for interface with profibus devices.
    • A Fault Tolerant Ethernet Bridge also provides the C300 controller access to Allen Bradley PLCs.
    • The FTEB is in a bridge chassis along with a downlink ControlNet interface card, which gives access to the Allen Bradley PLCs on a ControlNet.