C30+ Product Tank System

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to Lesson

Podcast

Play an AI-generated podcast conversation about this lesson
Download our mobile app to listen on the go
Get App

Questions and Answers

What is the purpose of the nitrogen blanket in TK-830, and from which equipment does it receive the nitrogen?

The nitrogen blanket in TK-830 is used to prevent moisture or oxygen contamination. It receives nitrogen from D-801.

Describe the function of M-830, including where it is located and why it is important for the C30+ product in TK-830.

M-830 is an internal mixer located in TK-830. Its purpose is to prevent settling/layering of sludge inside the tank and to maintain a homogeneous blend of different hydrocarbon densities.

Explain the purpose of the E-830 A/B/C heaters inside TK-830, specifying the heating medium used.

The purpose of E-830 A/B/C heaters are to maintain the temperature of the C30+ product tank (TK-830). They use 60 psig steam as the heating medium.

What is the function of P-830, and what type of pump is it?

<p>P-830 is a single-stage centrifugal pump that routes C30+ product from TK-830 to the C30+ Loading Rack.</p> Signup and view all the answers

What is the purpose of the D-801(Nitrogen Vent K.O. Drum) and what is the heating medium used?

<p>D-801 receives nitrogen from the Nitrogen Header, and P-801 routes the nitrogen to TK-800. D-801 has an internal heater E-801 that uses 60 psig steam as the heating element.</p> Signup and view all the answers

Flashcards

TK-830 (C30+ Product Tank)

A tank used to store the C30+ product, equipped with a mixer and heaters.

M-830 (C30+ Product Tank Mixer)

Installed internally in TK-830, this prevents settling and maintains a consistent mixture of hydrocarbons.

E-830A/B/C (C30+ Product Tank Heaters)

Internal heaters in TK-830 that maintain temperature using 60 psig steam.

P-830 (C30+ Loading Pump)

A pump that moves C30+ product from TK-830 to the C30+ Loading Rack.

Signup and view all the flashcards

F-830 (C30+ Product Filter)

It filters the C30+ product before it is sent to the loading rack.

Signup and view all the flashcards

Study Notes

  • TK-830 receives product from the bottom of T-430.
  • P-830 routes the C30+ product to F-830 and then to C30+ Loading Rack.
  • A nitrogen blanket from D-801 maintains the tank to prevent moisture or oxygen contamination.
  • M-830 is an internal mixer and E-830 is an internal heater.
  • Both are located within TK-830.
  • E-830 uses 60 psig steam as the heating medium.
  • A nitrogen blanket from D-801 maintains the tank to prevent moisture or oxygen contamination.
  • E-801 is an internal heater that uses 60 psig steam as the heating element.
  • D-801 gets nitrogen from the Nitrogen Header.
  • P-801 routes the nitrogen to TK-800.

TK-830 (C30+ Product Tank)

  • It measures 55’D x 48’L and has a cone roof, mixer, and heaters.
  • It stores C30+ product.
  • Product enters and exits the tank from the bottom.

M-830 (C30+ Product Tank Mixer)

  • M-830 is installed internally in TK-830.
  • It avoids settling/layering of sludge and maintains a homogeneous blend of different hydrocarbon densities.
  • It is driven by a 7.5 HP 12885 GPM induction electric motor.

E-830A/B/C (C30+ Product Tank Heaters)

  • E-830A/B/C are internal heaters on TK-830.
  • They maintain temperature using 60 psig steam as the heating medium.

P-830 (C30+ Loading Pump)

  • P-830 is a single-stage centrifugal pump.
  • It is driven by a 40 HP 3550 RPM horizontally-mounted, induction electric motor.
  • It routes C30+ product from TK-830 to C30+ Loading Rack.

F-830 (C30+ Product Filter)

  • F-830 filters the C30+ product prior to being routed to the C30+ Loading Rack.

D-801 (Nitrogen Vent K.O. Drum)

  • D-801 measures 6’D x 8’L and has an internal heater.
  • It knocks out any entrained liquid from the nitrogen to be supplied to the tanks.

E-801 (Nitrogen Vent K.O. Drum Heater)

  • E-801 is an internal heater on D-801.
  • It maintains temperature using 60 psig steam as the heating medium.

P-801 (Nitrogen Vent K.O. Drum Pump)

  • P-801 is a single-stage centrifugal pump.
  • It is driven by 2 HP 24 GPM horizontally-mounted, induction electric motor.
  • It routes liquid from the bottom of D-801 to TK-800.