Podcast
Questions and Answers
What is the purpose of the nitrogen blanket in TK-830, and from which equipment does it receive the nitrogen?
What is the purpose of the nitrogen blanket in TK-830, and from which equipment does it receive the nitrogen?
The nitrogen blanket in TK-830 is used to prevent moisture or oxygen contamination. It receives nitrogen from D-801.
Describe the function of M-830, including where it is located and why it is important for the C30+ product in TK-830.
Describe the function of M-830, including where it is located and why it is important for the C30+ product in TK-830.
M-830 is an internal mixer located in TK-830. Its purpose is to prevent settling/layering of sludge inside the tank and to maintain a homogeneous blend of different hydrocarbon densities.
Explain the purpose of the E-830 A/B/C heaters inside TK-830, specifying the heating medium used.
Explain the purpose of the E-830 A/B/C heaters inside TK-830, specifying the heating medium used.
The purpose of E-830 A/B/C heaters are to maintain the temperature of the C30+ product tank (TK-830). They use 60 psig steam as the heating medium.
What is the function of P-830, and what type of pump is it?
What is the function of P-830, and what type of pump is it?
What is the purpose of the D-801(Nitrogen Vent K.O. Drum) and what is the heating medium used?
What is the purpose of the D-801(Nitrogen Vent K.O. Drum) and what is the heating medium used?
Flashcards
TK-830 (C30+ Product Tank)
TK-830 (C30+ Product Tank)
A tank used to store the C30+ product, equipped with a mixer and heaters.
M-830 (C30+ Product Tank Mixer)
M-830 (C30+ Product Tank Mixer)
Installed internally in TK-830, this prevents settling and maintains a consistent mixture of hydrocarbons.
E-830A/B/C (C30+ Product Tank Heaters)
E-830A/B/C (C30+ Product Tank Heaters)
Internal heaters in TK-830 that maintain temperature using 60 psig steam.
P-830 (C30+ Loading Pump)
P-830 (C30+ Loading Pump)
Signup and view all the flashcards
F-830 (C30+ Product Filter)
F-830 (C30+ Product Filter)
Signup and view all the flashcards
Study Notes
- TK-830 receives product from the bottom of T-430.
- P-830 routes the C30+ product to F-830 and then to C30+ Loading Rack.
- A nitrogen blanket from D-801 maintains the tank to prevent moisture or oxygen contamination.
- M-830 is an internal mixer and E-830 is an internal heater.
- Both are located within TK-830.
- E-830 uses 60 psig steam as the heating medium.
- A nitrogen blanket from D-801 maintains the tank to prevent moisture or oxygen contamination.
- E-801 is an internal heater that uses 60 psig steam as the heating element.
- D-801 gets nitrogen from the Nitrogen Header.
- P-801 routes the nitrogen to TK-800.
TK-830 (C30+ Product Tank)
- It measures 55’D x 48’L and has a cone roof, mixer, and heaters.
- It stores C30+ product.
- Product enters and exits the tank from the bottom.
M-830 (C30+ Product Tank Mixer)
- M-830 is installed internally in TK-830.
- It avoids settling/layering of sludge and maintains a homogeneous blend of different hydrocarbon densities.
- It is driven by a 7.5 HP 12885 GPM induction electric motor.
E-830A/B/C (C30+ Product Tank Heaters)
- E-830A/B/C are internal heaters on TK-830.
- They maintain temperature using 60 psig steam as the heating medium.
P-830 (C30+ Loading Pump)
- P-830 is a single-stage centrifugal pump.
- It is driven by a 40 HP 3550 RPM horizontally-mounted, induction electric motor.
- It routes C30+ product from TK-830 to C30+ Loading Rack.
F-830 (C30+ Product Filter)
- F-830 filters the C30+ product prior to being routed to the C30+ Loading Rack.
D-801 (Nitrogen Vent K.O. Drum)
- D-801 measures 6’D x 8’L and has an internal heater.
- It knocks out any entrained liquid from the nitrogen to be supplied to the tanks.
E-801 (Nitrogen Vent K.O. Drum Heater)
- E-801 is an internal heater on D-801.
- It maintains temperature using 60 psig steam as the heating medium.
P-801 (Nitrogen Vent K.O. Drum Pump)
- P-801 is a single-stage centrifugal pump.
- It is driven by 2 HP 24 GPM horizontally-mounted, induction electric motor.
- It routes liquid from the bottom of D-801 to TK-800.
Studying That Suits You
Use AI to generate personalized quizzes and flashcards to suit your learning preferences.