What feature of the C200/C200E controller ensures no single point of failure when redundancy is implemented?

  • Dual-chassis structure (correct)
  • On-process migration
  • Single chassis configuration
  • Use of two separate power supplies
  • Which communication networks does the C200/C200E controller utilize to connect with the Experion Server?

  • Control Network and Fault Tolerant Ethernet (correct)
  • Ethernet and Modbus
  • Wireless and Serial
  • Fieldbus and ControlNet
  • What is the maximum Input Output unit capacity for the C200/C200E controller?

  • 128 units
  • 64 units (correct)
  • 32 units
  • 256 units
  • Which control method is NOT utilized by the C200/C200E controller?

    <p>Ladder logic</p> Signup and view all the answers

    What capability does the C200/C200E possess concerning peer-to-peer communication?

    <p>With Allen Bradley devices and ControlNet devices</p> Signup and view all the answers

    What is a key feature of Series H Input Output devices?

    <p>They feature galvanic isolation.</p> Signup and view all the answers

    Which of the following statements is true about the PM device?

    <p>It has been used for years with Honeywell controllers.</p> Signup and view all the answers

    In terms of Fieldbus connectivity, what is the maximum number of devices allowed per link?

    <p>16 devices</p> Signup and view all the answers

    What distinguishes a Hart device from Fieldbus?

    <p>It superimposes digital signals onto a 4-20 mA signal.</p> Signup and view all the answers

    How many C200E controllers can be simulated using the Experion PKS in one Windows machine?

    <p>Four C200E controllers</p> Signup and view all the answers

    What limitation is placed on the combination of devices used in a C200/C200E controller?

    <p>Must not exceed 64 Input Output units.</p> Signup and view all the answers

    What kind of interface does the Fieldbus Interface Module connect to?

    <p>A Fieldbus termination panel</p> Signup and view all the answers

    Which of the following is NOT compatible with redundancy in the PMIO modules?

    <p>HART</p> Signup and view all the answers

    Which of the following best describes the simulation process for Input Output in Experion PKS?

    <p>It can utilize both simple and complex simulation models.</p> Signup and view all the answers

    Study Notes

    C200/C200E Overview

    • The C200/C200E is a process controller fully integrated with the Experion Server.
    • It is redundant-capable, meaning it offers optional redundancy features.
    • Redundancy can be achieved with two separate chassis or a single chassis with a redundant power supply.
    • It supports both ControlNet and Fault Tolerant Ethernet (FTE) networks.
    • On-process migration is an available option, requiring a redundant controller.
    • C200/C200E has a single control execution set with flexibility for regulatory, logic, device, and sequence control.
    • It uses function blocks instead of ladder logic for control.
    • It can execute control actions as fast as 5 milliseconds.
    • It supports up to 64 Input Output (I/O) units, allowing for mixing and matching of different I/O families.
    • C200/C200E was developed in partnership with Allen-Bradley, allowing peer-to-peer communication with Allen-Bradley devices and other ControlNet devices.

    C200/C200E & ACE Network Connections

    • The C200/C200E controller communicates with the Experion Server and the Experion ACE node through ControlNet (CNet) and Fault Tolerant Ethernet (FTE).

    C200/C200E I/O Options

    • ControlNet is used for I/O communication, supporting Allen-Bradley I/O modules (Series A and H).
    • Series H modules are designed for hazardous environments.
    • Allen-Bradley also offers chassis I/O modules that fit in the same footprint as the C200/C200E, connecting via ControlNet.
    • For redundant I/O, PMIO modules can be used in conjunction with 10 link interface modules.
    • The C200/C200E can be configured for Foundation Fieldbus devices using a Fieldbus Interface Module (FIM).
    • FIM connects to termination panels with up to two Fieldbus links, each holding up to 16 devices.
    • Hart devices, similar to Fieldbus, support additional information through a superimposed digital signal on a 4-20 mA signal.
    • Hart devices can be connected through chassis I/O and PMIO, offering redundancy options.
    • Profibus and DeviceNet interface modules are also available, allowing the C200/C200E to connect to respective devices.

    Experion Simulation Control Environment

    • Experion PKS (Process Knowledge Server) simulates a C200E controller, executing SCM and CM devices.
    • A single Windows machine can simulate up to four C200E controllers.
    • Simulation can be achieved through simplified tie-back models or complex simulations.
    • Control Builder, integrated with Configuration Studio, is used for both C200/C200E configuration and simulation.
    • Existing configurations can be reused and transferred from simulation to real controllers.
    • Simulation Control Environment is separately licensed and must be installed on a separate node, not a server or station.

    ACE

    • Application Control Environment (ACE) is a Windows machine connected to the FTE.
    • ACE supports advanced control and optimization.
    • It uses the same Control Execution Environment as C200/C200E, C300, and UOC/vUOC.
    • ACE offers peer-to-peer communication to all these controllers and their simulations (except SIM-C200).
    • It also features peer-to-peer connections with the FIM, TPS (for optimization), and third-party OPC servers.
    • Custom Algorithm Block (CAB), used for writing customized control programs, can be implemented on an ACE node.

    SIM-ACE

    • SIM-ACE is a simulated ACE node used for strategy checkout before going on-process.
    • It supports reading system data and offers access to all the peer-to-peer options available in a genuine ACE.
    • However, it does not have the ability to write.
    • It is used to debug VB.NET CAB applications.
    • It is strongly recommended to check CAB strategies using SIM-ACE before going online.

    Studying That Suits You

    Use AI to generate personalized quizzes and flashcards to suit your learning preferences.

    Quiz Team

    Related Documents

    Description

    Explore the features and capabilities of the C200/C200E process controller, fully integrated with the Experion Server. This quiz covers its redundancy options, supported networks, control execution, and I/O capabilities. Gain insights into its function block usage and compatibility with Allen-Bradley devices.