Boiler Blowoff and Drainage Quiz
15 Questions
1 Views

Choose a study mode

Play Quiz
Study Flashcards
Spaced Repetition
Chat to lesson

Podcast

Play an AI-generated podcast conversation about this lesson

Questions and Answers

What is the minimum pressure rating required for blowoff or drain valves used in low-pressure steam boilers?

  • 150 kPa (22 psi)
  • 200 kPa (30 psi) (correct)
  • 250 kPa (36 psi)
  • 100 kPa (15 psi)
  • Where is the blowoff connection located in packaged firetube boilers?

  • At the bottom of the shell close to the back end (correct)
  • On the side of the shell
  • At the top of the shell close to the front end
  • At the middle of the shell
  • Which fittings are required by ASME BPVC IV on every hot water heating boiler?

  • Expansion tanks and safety relief valves
  • Soot blowers and economizers
  • Flowmeters and check valves
  • Pressure gauges and altitude indicators (correct)
  • Where are blowoff connections typically located in boilers with water legs?

    <p>At the lowest point of each water leg</p> Signup and view all the answers

    What is the minimum temperature rating required for valves used to blowoff or drain low-pressure steam boilers?

    <p>120°C (250°F)</p> Signup and view all the answers

    What is the purpose of an expansion tank in a heating system?

    <p>To compress the air cushion inside the tank</p> Signup and view all the answers

    According to ASME BPVC IV Part HG-709.2, what is a requirement for expansion tanks in systems designed to operate above 200 kPa?

    <p>They must have a minimum hydrostatic test pressure of 520 kPa</p> Signup and view all the answers

    What is the purpose of isolation and drain valves in the piping to a bladder-style expansion tank?

    <p>To allow draining the tank without emptying the system</p> Signup and view all the answers

    How does oxygen dissolved in the water in non-bladder style expansion tanks affect the heating system?

    <p>It can cause corrosion of steel piping and heating units</p> Signup and view all the answers

    What does the presence of a shutoff valve in the connecting line between the tank and the hot water supply header allow?

    <p>Draining the tank without emptying the system</p> Signup and view all the answers

    What type of gauge is used to indicate whether the hot water system is full?

    <p>Altitude gauge</p> Signup and view all the answers

    What is the purpose of an expansion tank in a hot water heating system?

    <p>To store excess water due to expansion</p> Signup and view all the answers

    What is a unique requirement for safety relief valves in hot water heating boilers?

    <p>The additional valves may be set to higher than the maximum allowable working pressure (MAWP)</p> Signup and view all the answers

    What is the purpose of stop valves in hot water heating boilers?

    <p>To allow draining of the boiler without emptying the entire piping system</p> Signup and view all the answers

    Why are siphons not required between the gauge and the boiler in hot water service?

    <p>Because hot water boilers are completely filled with water and generate no steam</p> Signup and view all the answers

    More Like This

    CSA B51 Boiler
    30 questions
    Boiler Inspection and Compliance Quiz
    30 questions
    Ohio Boiler Test Flashcards
    100 questions

    Ohio Boiler Test Flashcards

    WellRegardedObsidian1129 avatar
    WellRegardedObsidian1129
    Boiler Systems and Safety Regulations
    60 questions
    Use Quizgecko on...
    Browser
    Browser