Podcast
Questions and Answers
section 16 apply on : a) class 1 and class 2 remote control circuits, b) class 1 and class 2 signal circuits, c) class1 extra low-voltage power circuits d) class 2 low-energy power circuits. Rule: 16-000 (scope)
section 16 apply on : a) class 1 and class 2 remote control circuits, b) class 1 and class 2 signal circuits, c) class1 extra low-voltage power circuits d) class 2 low-energy power circuits. Rule: 16-000 (scope)
True
Class 1 extra-low-voltage power circuits shall be supplied from a source having a rated output of not more than 30 V and 1000 V.A ( Rule: 16-100)
Class 1 extra-low-voltage power circuits shall be supplied from a source having a rated output of not more than 30 V and 1000 V.A ( Rule: 16-100)
True
Class 1 remote control and signal circuits shall be supplied by a source not exceeding 600 V. ( Rule-16-100(2))
Class 1 remote control and signal circuits shall be supplied by a source not exceeding 600 V. ( Rule-16-100(2))
True
overcurrent protection is not required on the secondary side of the transformer to protect the secondary conductors, but overcurrent protection is required for branch-circuit panelboards. (source: google)
overcurrent protection is not required on the secondary side of the transformer to protect the secondary conductors, but overcurrent protection is required for branch-circuit panelboards. (source: google)
Signup and view all the answers
In class 1 circuits, the overcurrent devices shall be located at the point where the conductor to be protected receives its supply and overcurrent device shall be permitted to be an integral part of the power supply.( Rule: 16-106)
In class 1 circuits, the overcurrent devices shall be located at the point where the conductor to be protected receives its supply and overcurrent device shall be permitted to be an integral part of the power supply.( Rule: 16-106)
Signup and view all the answers
1000 V.A limitation, class 1 extra-low-voltage power circuit sources including transformers shall not exceed 2500 V.A and product of maximum current and voltage not exceed 10 000 V.A with the overcurrent protection bypassed. ( Rule: 16-108)
1000 V.A limitation, class 1 extra-low-voltage power circuit sources including transformers shall not exceed 2500 V.A and product of maximum current and voltage not exceed 10 000 V.A with the overcurrent protection bypassed. ( Rule: 16-108)
Signup and view all the answers
Insulated conductors smaller than no. 14 AWG copper shall be permitted to be used in class1, circuit if,
a) installed in a raceway ( an enclosed conduit that forms a physical pathway for electrical wiring)
b) installed as a cable assembly; or
c) within a flexible cord in accordance with ( Rule: 12-402 )
Insulated conductors smaller than no. 14 AWG copper shall be permitted to be used in class1, circuit if, a) installed in a raceway ( an enclosed conduit that forms a physical pathway for electrical wiring) b) installed as a cable assembly; or c) within a flexible cord in accordance with ( Rule: 12-402 )
Signup and view all the answers
subject to the condition, insulated conductors shall be not smaller than
a) No. 16 AWG for individual insulated conductors pulled in raceways;
b) No. 18 AWG for individual insulated conductors laid in raceways;
c) No. 18 AWG for an integral assembly of two or more insulated conductors. (Rule: 16-110(2)
subject to the condition, insulated conductors shall be not smaller than a) No. 16 AWG for individual insulated conductors pulled in raceways; b) No. 18 AWG for individual insulated conductors laid in raceways; c) No. 18 AWG for an integral assembly of two or more insulated conductors. (Rule: 16-110(2)
Signup and view all the answers
1.Different Class 1 circuits shall be permitted to occupy the same enclosure, cable, or raceway without regard to whether the individual circuits are AC or DC
2. Insulated power circuits and insulated conductors of class 1 circuits shall not be permitted in the same enclosure, cable or raceway except when they are connected to the same equipment. (Rule: 16-114)
1.Different Class 1 circuits shall be permitted to occupy the same enclosure, cable, or raceway without regard to whether the individual circuits are AC or DC 2. Insulated power circuits and insulated conductors of class 1 circuits shall not be permitted in the same enclosure, cable or raceway except when they are connected to the same equipment. (Rule: 16-114)
Signup and view all the answers
All insulated conductors of such remote control circuits shall be installed in conduit or electrical metallic tubing or be otherwise suitable protected from mechanical damage or other harmful conditions such as moisture, excessive heat or corrosive action (The proposed infrared or IR remote control circuit can be used to operate an appliance ON/OFF through any standard TV remote control handset)( Rule: 16-116)
All insulated conductors of such remote control circuits shall be installed in conduit or electrical metallic tubing or be otherwise suitable protected from mechanical damage or other harmful conditions such as moisture, excessive heat or corrosive action (The proposed infrared or IR remote control circuit can be used to operate an appliance ON/OFF through any standard TV remote control handset)( Rule: 16-116)
Signup and view all the answers
Class 2 circuits, 0 to 20 V, the open-circuit voltage does not exceed 20 V shall have an overcurrent protection rating not exceeding 5 A (Rule: 16-200 (1) (a))
Class 2 circuits, 0 to 20 V, the open-circuit voltage does not exceed 20 V shall have an overcurrent protection rating not exceeding 5 A (Rule: 16-200 (1) (a))
Signup and view all the answers
A circuit does not need overcurrent protection when:
a) The current is supplied from batteries and not exceeding 7.5 A after 1 min.
b) a transformer or other power supply device having a class 2 output
) a current not exceeding 5 A .
A circuit does not need overcurrent protection when: a) The current is supplied from batteries and not exceeding 7.5 A after 1 min. b) a transformer or other power supply device having a class 2 output ) a current not exceeding 5 A .
Signup and view all the answers
A device having energy- limiting characteristics shall be permitted to consist of a series resistor of suitable rating or other similar device. ( Rule: 16-200(2))
A device having energy- limiting characteristics shall be permitted to consist of a series resistor of suitable rating or other similar device. ( Rule: 16-200(2))
Signup and view all the answers
A class 2 power supply shall not connected in series or parallel with another class 2 power source. (Rule: 16-200(3))
A class 2 power supply shall not connected in series or parallel with another class 2 power source. (Rule: 16-200(3))
Signup and view all the answers
A device having a class 2 output shall be permitted for use as a device energy limiting characteristics. Rue ; 16-200(4))
A device having a class 2 output shall be permitted for use as a device energy limiting characteristics. Rue ; 16-200(4))
Signup and view all the answers
Transformers or other devices having class 2 outputs shall be protected on the supply side by an overcurrent device with a rating or setting not exceeding 20 A. ( Rule: 16-202(2))
Transformers or other devices having class 2 outputs shall be protected on the supply side by an overcurrent device with a rating or setting not exceeding 20 A. ( Rule: 16-202(2))
Signup and view all the answers
A class 2 power supply unit shall have permanent markings that are readily visible after installation to indicates:
a) the class of supply and its electrical rating
b) suitability for wet locations when intended for we locations. ( Rule: 16-204)
A class 2 power supply unit shall have permanent markings that are readily visible after installation to indicates: a) the class of supply and its electrical rating b) suitability for wet locations when intended for we locations. ( Rule: 16-204)
Signup and view all the answers
over current shall not be an interchangeable type and it shall be an integral part of a transformer or other power supply device.(Rule: 16-208)
over current shall not be an interchangeable type and it shall be an integral part of a transformer or other power supply device.(Rule: 16-208)
Signup and view all the answers
overcurrent devices shall be located at the point where the insulated conductors to be protected receive their supply.(Rule: 16-208)
overcurrent devices shall be located at the point where the insulated conductors to be protected receive their supply.(Rule: 16-208)
Signup and view all the answers
The maximum allowable current shall be as listed in Table 57 for sizes No. 16 and smaller and current limitation should be exceed 5 A ( Rule: 16-210(4).
The maximum allowable current shall be as listed in Table 57 for sizes No. 16 and smaller and current limitation should be exceed 5 A ( Rule: 16-210(4).
Signup and view all the answers
Eight conductor cable for class 2 power and data communication circuits shall be permitted for use in accordance with Table 60. (Rule: 16-210(7)).
Eight conductor cable for class 2 power and data communication circuits shall be permitted for use in accordance with Table 60. (Rule: 16-210(7)).
Signup and view all the answers
Insulated conductors and cables of class 2 circuits shall be separated from insulated conductors of electric lighting and power ( Rule: 16-212 (1))
Insulated conductors and cables of class 2 circuits shall be separated from insulated conductors of electric lighting and power ( Rule: 16-212 (1))
Signup and view all the answers
Class 1 circuits operating at 300 V or less at least from insulated conductors of electric lighting and power
Class 1 circuits operating at 300 V or less at least from insulated conductors of electric lighting and power
Signup and view all the answers
Where electric lighting or power conductors are bare, all class 2 circuit insulted conductors and cables in the same room or space shall be enclosed in a metal raceway that is bonded to ground, and no opening such as an outlet box shall be permitted to be located within 2 of the bare conductors and including 15 kV or within 3 m of bare conductors above 15 kV.
Where electric lighting or power conductors are bare, all class 2 circuit insulted conductors and cables in the same room or space shall be enclosed in a metal raceway that is bonded to ground, and no opening such as an outlet box shall be permitted to be located within 2 of the bare conductors and including 15 kV or within 3 m of bare conductors above 15 kV.
Signup and view all the answers
Direct buried class 2 circuits shall be:
- the class 2 circuit is in a metal-sheathed cable, with the sheath bonded to ground.
- the power circuit operate at 750 V or less
- all cables are insulated for the maximum voltage of any cable in the trench. ( Rule: 16-226)
Direct buried class 2 circuits shall be:
- the class 2 circuit is in a metal-sheathed cable, with the sheath bonded to ground.
- the power circuit operate at 750 V or less
- all cables are insulated for the maximum voltage of any cable in the trench. ( Rule: 16-226)
Signup and view all the answers
Cable bundle
Cable bundle
Signup and view all the answers
A class 2 power and data communication circuit shall be supplied from power sourcing equipment with an output limited to:
A class 2 power and data communication circuit shall be supplied from power sourcing equipment with an output limited to:
Signup and view all the answers
Table 60 base on :
a)the size of conductor
b) the cable temperature rating
c) the number of cables in a cable bundle in contact with each other
d) the smallest conductor size and lowest temperature rating of any cable in the cable bundle.( Rule: 16-330(3)
Table 60 base on : a)the size of conductor b) the cable temperature rating c) the number of cables in a cable bundle in contact with each other d) the smallest conductor size and lowest temperature rating of any cable in the cable bundle.( Rule: 16-330(3)
Signup and view all the answers
not more than 192 cables shall be permitted to be bundle together ( 16-330(3)(b))
not more than 192 cables shall be permitted to be bundle together ( 16-330(3)(b))
Signup and view all the answers
The correction factors of table 5A shall apply where class 2 power and data communication circuit cables are installed in an ambient temperature exceeding 30'C. ( Rule: 16-330(5)
The correction factors of table 5A shall apply where class 2 power and data communication circuit cables are installed in an ambient temperature exceeding 30'C. ( Rule: 16-330(5)
Signup and view all the answers
Where more than one cable bundle is installed in a ventilated and ladder-type cable tray, cable bundles shall be spaced at not less than :
Where more than one cable bundle is installed in a ventilated and ladder-type cable tray, cable bundles shall be spaced at not less than :
Signup and view all the answers
cables for class 2 power and data communication circuits shall not be required to comply with the cable bunding requirements where:
a) the rating of each output circuit supplied by power sourcing equipment cannot exceed 0.3 A to any load conductor
b) the cables have a minimum conductor size of 24 AWG. ( Rule: 16-330( 8) (a)(b)
cables for class 2 power and data communication circuits shall not be required to comply with the cable bunding requirements where: a) the rating of each output circuit supplied by power sourcing equipment cannot exceed 0.3 A to any load conductor b) the cables have a minimum conductor size of 24 AWG. ( Rule: 16-330( 8) (a)(b)
Signup and view all the answers
Class 1: less than 30 V and less than 1000 VA
Class 2: less than 150 V and less than 100 VA( source: google)
Class 1: less than 30 V and less than 1000 VA Class 2: less than 150 V and less than 100 VA( source: google)
Signup and view all the answers
What is one of the major differences between class 1 and class 2 circuits?
What is one of the major differences between class 1 and class 2 circuits?
Signup and view all the answers
Class 2 circuit: low voltage and current, and therefore low power that it does not present a fire hazard or a shock hazard to personnel.(source: google)
Class 2 circuit: low voltage and current, and therefore low power that it does not present a fire hazard or a shock hazard to personnel.(source: google)
Signup and view all the answers
example of a class 2 circuit: low-energy voice, sound, intercom, or public address systems, low-voltage lighting, PLCs, security systems, or thermostats.
example of a class 2 circuit: low-energy voice, sound, intercom, or public address systems, low-voltage lighting, PLCs, security systems, or thermostats.
Signup and view all the answers
Can you run class 1 and Class 2 wiring in the same conduit?
Ans: Class 1 and Class 2 wiring are not permitted in the same enclosure, cable, or raceway.
Can you run class 1 and Class 2 wiring in the same conduit? Ans: Class 1 and Class 2 wiring are not permitted in the same enclosure, cable, or raceway.
Signup and view all the answers
example of class 1 circuit: A class 1 circuit is the portion of wiring system between the load side of the overcurrent protection device (OPCD) or the power-limited supply and the connected load.
example of class 1 circuit: A class 1 circuit is the portion of wiring system between the load side of the overcurrent protection device (OPCD) or the power-limited supply and the connected load.
Signup and view all the answers
What voltage are class 1 circuit conductors rated for?
What voltage are class 1 circuit conductors rated for?
Signup and view all the answers